EnergonX UPS SOHO 12 [A010]-1

EnergonX
EnergonX
🔋12 V / 200 Ah AGM 2.4 kWh nominal energy 🔌1000 VA / 800 W 〰️Sine wave on battery 6 ms transfer 🔧10 A / 20 A charging 🧰EXPLORER frame

EnergonX UPS SOHO 12 [A010]-1

SKU: {EX1412-EXP-12 [A010]-1}

A fully assembled 12 V EnergonX UPS system with an EXPLORER frame, SPS SOHO SH1000 sine wave inverter and a 200 Ah Green Cell AGM VRLA battery. The system stores 2.4 kWh of nominal battery energy and provides up to 800 W continuous 230 V output power.

In battery mode it provides 220 V AC ±10%, 50 Hz ±1 Hz and a sine wave output. Transfer time during a mains failure is 6 ms. Charging current can be selected between 10 A and 20 A.

Fully assembled system: EXPLORER frame, SPS SOHO SH1000 inverter, Green Cell 12V 200Ah AGM VRLA battery, eight integrated M8 mounting points and the required EnergonX connector sets.
Optimised for UPS/standby operation: the inverter’s 13.8 V ±0.3 V charging voltage matches the Green Cell battery’s 13.5–13.8 V standby range. The configuration does not provide the 14.5–14.9 V cyclic charging voltage specified by the battery manufacturer, so it is intended primarily for standby UPS operation.
Brand:
EnergonX
Product code:
{EX1412-EXP-12 [A010]-1}
388.915 HUF
Netto price: 306.232 HUF
Piece (pc)
Piece (pc)
🔋12 V / 200 Ah AGM 2.4 kWh nominal energy 🔌1000 VA / 800 W 〰️Sine wave on battery 6 ms transfer 🔧10 A / 20 A charging 🧰EXPLORER frame

EnergonX UPS SOHO 12 [A010]-1

The EnergonX UPS SOHO 12 [A010]-1 is a fully assembled 12 V EnergonX UPS system with battery. It combines the mobile EXPLORER frame, the SPS SOHO SH1000 sine wave inverter, a 200 Ah Green Cell AGM VRLA battery, eight integrated M8 mounting points and the required EnergonX connector sets in one operational unit.

The system stores 2400 Wh, or 2.4 kWh, of nominal battery energy. During mains operation it powers the connected load and charges the battery; during a mains failure it transfers to battery operation in 6 ms.

Main benefits

Fully assembled EnergonX UPS systemThe battery, inverter, frame and required connection components form one operational unit.
2.4 kWh nominal battery energyThe Green Cell 12 V, 200 Ah AGM VRLA battery stores 2400 Wh of nominal energy.
1000 VA / 800 W outputSuitable for boilers, circulation pumps, control systems and smaller critical loads.
Sine wave battery outputIn battery mode it provides 220 V AC ±10% and 50 Hz ±1 Hz.
6 ms transfer timeTransfers rapidly to battery operation during a mains failure.
Maintenance-free AGM VRLA batterySealed design, no electrolyte top-up required, suitable for standby and cyclic applications.
10 A / 20 A charging currentThe 20 A setting is suitable for 200 Ah capacity, while 10 A provides slower charging.
Modular EXPLORER frameThe mobile frame and eight integrated M8 mounting points provide stable installation and future expansion options.
Not a BASE version: this version is supplied as a fully assembled, operational EnergonX UPS unit with battery, inverter and the listed connection and mounting components.

System configuration

System componentDescriptionSKU / status
FrameFRAME – EXPLORER{EX-EXP-VÁZ}
External UPS / inverterSPS SOHO SH1000No data
BatteryAGM Battery for UPS 12V200Ah{EX2200-A010}
M8 mounting pointIntegrated, 8 pcs{EX2100-QBRM8I}
Connector setQS Custom Connectors Set 3{EX2100-QBRCC}
UPS connector setAccessory – UPS connector set{EX2100-UPSHT120}

Green Cell 12 V 200 Ah AGM VRLA battery

The installed Green Cell AGM12V200AH-J is a sealed, maintenance-free VRLA AGM battery. The electrolyte is retained in glass-fibre separators, so no fluid top-up is required, and the manufacturer specifies it for both standby and cyclic operation.

200 Ah capacity2400 Wh, or 2.4 kWh, of nominal energy storage at 12 V.
IP54 battery enclosureManufacturer-rated protection against dust and splashing water for the battery itself.
M8 threaded terminalsFor stable high-current mechanical and electrical connection.
Up to 10 years service lifeManufacturer specification; actual service life depends on operating mode, depth of discharge and temperature.

⚠ High short-circuit current

2700 A manufacturer-rated short-circuit current: accidental shorting of the battery terminals can cause severe burns, electric arcing, fire and melted connections. Correct fusing, touch protection and insulated tools are essential.

Charging match and intended operating mode

The Green Cell battery’s standby charging voltage is 13.5–13.8 V, while the SPS SOHO SH1000 charging voltage is 13.8 V ±0.3 V. Because the ranges overlap, this combination is primarily suitable for standby UPS and buffer operation.

For cyclic charging, Green Cell specifies 14.5–14.9 V. The SH1000 built-in charger does not provide this voltage, so the system should not be regarded as an optimal frequently deep-cycled AGM solution. For regular deep-discharge use, a separate charging method providing the manufacturer-specified cyclic voltage may be required.

Recommended 20 A charging currentApproximately 0.1 C for 200 Ah capacity and well below the manufacturer’s 60 A maximum.
Selectable 10 A charging currentGentler charging, but potentially around twice the charging time.
Charging time: actual charging time cannot be calculated simply by dividing capacity by charging current, because charging current may change during the process and an AGM battery draws progressively less current near full charge.

UPS function and 230 V power supply

The SPS SOHO SH1000 is rated at 1000 VA / 800 W. In battery mode it provides 220 V AC ±10%, 50 Hz ±1 Hz and a sine wave output. During normal mains operation, output frequency and waveform follow the incoming mains supply.

The unit provides both UPS and inverter modes. The mains input voltage range is 120–300 V AC in inverter mode and 145–285 V AC in UPS mode. Transfer time from mains to battery operation is 6 ms.

Protection functions: overload, short-circuit and overtemperature protection, battery circuit breaker and front-panel LEDs for mains, charging, battery and fault status.

Runtime example – modern boiler and circulation pump

The following illustrative calculation uses a modern condensing boiler with 113 W maximum electrical consumption and a high-efficiency circulation pump with 40 W maximum consumption, for a combined continuous load of 153 W.

Calculation stepValueNotes
Nominal battery energy2400 Wh12 V × 200 Ah.
Battery-friendly depth of discharge50%The example uses half the nominal energy to support AGM service life.
Assumed usable DC energy2400 Wh × 50% = 1200 WhIllustrative calculation value.
Assumed inverter efficiency80%Example assumption, not a guaranteed efficiency at every load point.
Estimated usable 230 V energy1200 Wh × 80% = 960 WhAfter inverter losses.
Combined boiler and pump load153 W113 W boiler + 40 W pump.
Estimated battery-friendly continuous runtime960 Wh ÷ 153 W ≈ 6.3 hoursCalculated at continuous maximum reference load.
Example result: at 50% depth of discharge and an assumed 80% inverter efficiency, the system can continuously power a 113 W boiler and a circulation pump consuming up to 40 W for approximately 6.3 hours.
Actual runtime may differ: real AGM capacity depends on discharge current, temperature, age and condition. Deeper discharge may provide longer one-time runtime but can accelerate battery wear. Partial-load and intermittent boiler/pump operation may increase actual runtime.

EXPLORER frame, mounting and connections

The 54 kg battery and SPS SOHO SH1000 unit are integrated into one mobile system on the EXPLORER frame. Eight integrated M8 mounting points provide stable mechanical fixing and future expansion options.

The QS Custom Connectors Set 3 and dedicated UPS connector set form part of the finished system’s connection architecture. The accessible position of the external inverter facilitates operation, ventilation, inspection and professional maintenance.

High total weight: the calculated combined weight of the main components is approximately 79.2 kg. The system should preferably be moved on its wheeled frame; manual lifting may require several people or suitable lifting equipment.

Main technical specifications

The table summarises the main data for the complete system, the Green Cell AGM battery and the SPS SOHO SH1000 unit. Where no verified value is available, “No data” is shown.
ParameterValueNotes
SKU{EX1412-EXP-12 [A010]-1}EnergonX finished-product item number.
Product nameEnergonX UPS SOHO 12 [A010]-1“SOHO” refers to the installed SPS SOHO inverter family, “12” to the system voltage and “A010” to the installed battery type.
Product familyEnergonX UPSFully assembled EnergonX UPS unit with battery.
System voltage12 V DCWith one 12 V AGM battery.
Battery webshop nameAGM Battery for UPS 12V200Ah{EX2200-A010}
Battery manufacturerGreen CellManufacturer data.
Manufacturer product codeAGM12V200AH-JManufacturer data.
EAN5904326376311Manufacturer data.
Battery technologyVRLA AGMSealed, maintenance-free lead-acid battery.
Nominal battery voltage12 VManufacturer data.
Nominal battery capacity200 AhManufacturer data.
Nominal stored energy2400 Wh / 2.4 kWh12 V × 200 Ah.
Battery operating modeStandby and cyclic operationThe manufacturer also lists UPS, marine, solar and photovoltaic applications.
Expected battery service lifeup to 10 yearsManufacturer specification; depends on operating and environmental conditions.
Internal resistance≤5 mΩ at 25 °CManufacturer data.
Short-circuit current2700 AManufacturer data; extremely high prospective fault current.
Standby charging voltage13.5–13.8 VTemperature compensation: −20 mV/°C according to manufacturer data.
Cyclic charging voltage14.5–14.9 VTemperature compensation: −30 mV/°C according to manufacturer data.
Maximum charging current60 AManufacturer data.
Battery terminalM8 threaded terminalManufacturer data.
Battery IP ratingIP54Does not define the IP rating of the complete assembled system.
Maintenance requirementMaintenance-freeSealed VRLA AGM design; no electrolyte top-up required.
Installation positionCan operate in multiple positionsElectrolyte is retained in glass-fibre separators; manufacturer installation requirements must be followed.
External UPS / inverter modelSPS SOHO SH1000Model-specific datasheet version.
Rated apparent power1000 VAManufacturer data.
Rated active power800 WManufacturer data.
Power factor0.8Manufacturer data.
Output voltage in battery mode220 V AC ±10%Manufacturer data.
Output frequency in battery mode50 Hz ±1 HzManufacturer data.
Output waveform in battery modeSine waveManufacturer data.
Transfer time6 msManufacturer data.
ProtectionOverload, short circuit, overtemperatureManufacturer data.
Noise level55 dB at 1 metreManufacturer data.
UPS charging voltage13.8 V ±0.3 VMatches the battery’s standby charging range.
Selectable UPS charging current10 A or 20 ABoth values are below the Green Cell battery’s 60 A maximum charging current.
Recommended charging-current setting20 ASuitable for 200 Ah capacity, approximately 0.1 C; 10 A provides slower charging.
Charging applicationPrimarily UPS/standby operationThe SOHO charger does not reach the 14.5–14.9 V cyclic charging voltage specified by the manufacturer.
UPS operating temperature0–40 °CManufacturer data.
UPS operating humidity20–95%, non-condensingManufacturer data.
EXPLORER frame external dimensions641 × 485 × 660 mmEnergonX frame data.
Battery dimensions240 × 522 × 226 mmManufacturer dimension order; total height with terminals 226 mm.
External SH1000 unit dimensions313 × 295 × 189 mmWidth × depth × height.
Overall system dimensionsNo data
EXPLORER frame weightapprox. 10.2 kgEnergonX frame data.
Battery weight54.0 kgManufacturer data.
External SH1000 unit weight15.0 kgManufacturer data.
Calculated combined weight of main componentsapprox. 79.2 kgSum of the stated EXPLORER frame, battery and SH1000 unit weights.
Actual total system weightNo dataThe finished product may be slightly heavier because of connectors, cables and smaller fittings.
Integrated M8 mounting points8For mechanically securing accessories and fittings.
Connector setsQS Custom Connectors Set 3 + UPS connector setIncluded in the assembled system.
Complete-system IP ratingNo data

Recommended applications

  • Backup power for gas boilers, circulation pumps and heating controllers.
  • Smaller critical loads in institutional, industrial or agricultural applications.
  • Routers, modems, network equipment, camera systems and communication devices.
  • Computers, controllers, monitoring systems and smaller technical electronic equipment.
  • Lighting, gate control, security equipment and other loads requiring up to 800 W continuous power.
  • Locations requiring high-capacity, maintenance-free AGM backup energy.
Loads with high starting current: motors, pumps, fans and transformer-based equipment may draw several times their rated power during start-up. Starting peak demand must be checked in addition to the 800 W continuous-power limit.

Safety and installation warning

230 V mains voltage: system installation and use with building-services equipment must be checked by a qualified electrician. Opening the enclosure creates an electric-shock hazard.
Stand-alone output: the load must be connected directly to the inverter output. The output must not be connected to or backfeed the building’s existing electrical installation.
High-current 12 V system: the 200 Ah AGM battery can deliver extremely high fault current. Fusing, cables, connectors and mechanical protection must be designed accordingly.
Ventilation: use indoors in a dry, dust-free and well-ventilated location. The inverter fan and ventilation openings must remain unobstructed.
Protective earthing: the inverter protective-earth connection must be installed correctly.
Load limit: the combined continuous 230 V load must not exceed 800 W. Starting peak power must be considered separately for every load.
Battery handling: never short the terminals. Use insulated tools and appropriate personal protective equipment. Do not use a damaged, deformed or leaking battery.
Not for life-safety applications: not suitable for direct life-support medical equipment, lifting equipment, traffic-control systems, aviation systems or other safety-critical applications.
Repair and modification: do not open, modify or attempt to repair the inverter, battery or high-current connections.